In this research, the active PCM storage units could store solar energy in cold seasons or free night cooling in warm seasons for later use and hence reduce the heating/cooling load requirements. An accumulative heating energy savings of 40% in May and 10.3% in June/July 2019, were achieved.
There are five PCM related projects included in Task 32: Three projects deal with macro-encapsulated PCM containers in water stores. All of these projects include the development of TRNSYS models for the PCM stores: • At Lleida University, Spain, bottles of PCM material with graphite matrix for the
All models were used for yearly system simulations including PCM storage. With these models there is now the opportunity to develop optimized systems with various PCM store, hydraulic and control configurations and to compare PCM heat store systems with water heat store systems.
They compared the PCM storage tank to a water tank. PCM tank was filled with a commercial macro-encapsulated PCM (salt hydrate, 10 °C melting point) and provided nearly 15% more cold than a water tank, moreover, it maintained desired indoor temperature 20% longer. On the other hand, it took 4.5 times longer to charge the PCM tank.
German storage tank manufacturer Rubitherm offers a wide portfolio of thermal storage tanks for residential applications using PCMs. The company uses both inorganic PCMs (mixtures of different salts and water) and organic PCMs (produced from vegetable oils or
Possible Applications in Solar Buildings for PCM are • Cold storage for solar assisted cooling applications (PCT around 5 -18°C) • PCM (Micro-Capsules) incorporated in wall material (PCT around 22°C) • Heating storage for Solar Energy and
German storage tank manufacturer Rubitherm offers a wide portfolio of thermal storage tanks for residential applications using PCMs. The company uses both inorganic PCMs (mixtures of different salts and water) and
Laboratory Prototypes of PCM Storage Units A Report of IEA Solar Heating and Cooling programme - Task 32 "Advanced storage concepts for solar and low energy buildings" European Commission New Zealand Germany Norway A total of 39 Tasks have been initiated, 30 of which have been completed. Each Task is managed by
The utilization of the PCM storage tank for cooling applications resulted in energy savings of approximately 30 % between March and April, considering the weather conditions in New Zealand. Additionally, they compared the performance of using PCM in passive applications (in building walls) versus active applications (in the storage unit).
In their proposed approach, a phase change material (PCM) storage tank is charged from 5 to 8 using a cooling system, and then discharged from 13 to 16. The findings reveal that utilizing a 400 kg PCM with a melting temperature of 19 °C can meet the cooling requirements of a 73.8 m 2 building during hot summer days. Gholami and Farid [
The results indicated that the addition of a PCM storage tank can boost the COP of the system during on-peak hours by up to 86.34 %. An alternative method to reduce electric peak load is by improving the performance of vapor compression refrigeration systems (VCRS) during on-peak hours.
They compared the PCM storage tank to a water tank. PCM tank was filled with a commercial macro-encapsulated PCM (salt hydrate, 10 °C melting point) and provided nearly 15% more cold than a water tank, moreover, it maintained desired indoor temperature 20% longer. On the other hand, it took 4.5 times longer to charge the PCM tank.
In the case of PCM, heat storage capacity increased by 14% with basically no volume increase. It means that such storage units can be more compact and therefore appropriate for cases with space limitation. Besides, COP was higher, heating time was shortened and water temperature uniformity was good. Fig. 6.
Subsequently, the impacts of the number of PCM storage tank pipes on the system performance are analyzed. Following that, the influences of the pipe length on the system performance are investigated. It should be noted that in the base case, the number and length of pipes are considered to be 20 and 1 m, respectively.
The PCM was filled in the annular cavity between the outer wall of the water tank and the steel casing. Fins were welded on the outer wall of the water tank to increase the heat transfer performance. The condenser coil was wrapped around and affixed to the outside of the water tank which is coated by PCM.